Should Electronic Faucets Be Recommended in Hospitals?

Published online by Cambridge University Press:  02 January 2015

Iris F. Chaberny*
Affiliation:
Institute of Medical Microbiology and Hospital Epidemiology, Medical School Hannover, Hannover, Germany
Petra Gastmeier
Affiliation:
Institute of Medical Microbiology and Hospital Epidemiology, Medical School Hannover, Hannover, Germany
*
Medical School Hannover, Institute of Medical Microbiology and Hospital Epidemiology, Carl-Neuberg-Str. 1, D-30625 Hannover, Germany

Abstract

Microbiological examinations of electronic faucets newly installed in a hospital kitchen revealed high bacteria counts and Pseudomonas aeruginosa during a 6-month period of observation. Our data suggest that the use of electronic faucets poses a potential risk for nosocomial infection in high-risk areas of hospitals.

Type
Concise Communications
Copyright
Copyright © The Society for Healthcare Epidemiology of America 2004

Access options

Get access to the full version of this content by using one of the access options below. (Log in options will check for institutional or personal access. Content may require purchase if you do not have access.)

References

1. Halabi, M, Wiesholzer-Pittl, M, Schoberl, J, Mittermayer, H. Non-touch fittings in hospitals: a possible source of Pseudomonas aeruginosa and Legionella spp. J Hosp Infect 2001;49:117121.CrossRefGoogle ScholarPubMed
2. Hargreaves, J, Shireley, L, Hansen, S, et al. Bacterial contamination associated with electronic faucets: a new risk for healthcare facilities. Infect Control Hosp Epidemiol 2001;22:202205.CrossRefGoogle ScholarPubMed
3. Leprat, R, Denizot, V, Bertrand, X, Talon, D. Non-touch fittings in hospitals: a possible source of Pseudomonas aeruginosa and Legionella spp. J Hosp Infect 2003:53:77.CrossRefGoogle ScholarPubMed
4. Anonymous. Verordnung über die Qualitat von Wasser für den menschlichen Gebrauch (Trinkwasserverordnung – TrinkwV 2001). Bundesgesetzblatt 2001;24:959980.Google Scholar
5. Mermel, LA, Josephson, SL, Dempsey, J, Parenteau, S, Perry, C, Magill, N. Outbreak of Shigella sonnei in a clinical microbiology laboratory. J Clin Microbiol 1997;35:31633165.CrossRefGoogle Scholar
6. Bures, S, Fishbain, JT, Uyehara, CF, Parker, JM, Berg, BW. Computer keyboards and faucet handles as reservoirs of nosocomial pathogens in the intensive care unit. Am f Infect Control 2000;28:465471.CrossRefGoogle ScholarPubMed
7. Griffith, CJ, Malik, R, Cooper, RA, Looker, N, Michaels, B. Environmental surface cleanliness and the potential for contamination during handwashing. Am J Infect Control 2003;31:9396.CrossRefGoogle ScholarPubMed
8. Kerr, JR, Moore, JE, Curran, MD, et al. Investigation of a nosocomial outbreak of Pseudomonas aeruginosa pneumonia in an intensive care unit by random amplification of polymorphic DNA assay. J Hosp Infect 1995;30:125131.CrossRefGoogle Scholar
9. Assadian, O, El-Madani, N, Seper, E, et al. Sensor-operated faucets: a possible source of nosocomial infection? Infect Control Hosp Epidemiol 2002;23:4446.CrossRefGoogle ScholarPubMed