Persistence of the Same Strain of Legionella pneumophila in the Water System of an Italian Hospital for 15 Years

Published online by Cambridge University Press:  02 January 2015

M. Scaturro*
Affiliation:
Department of Infectious, Parasitic, and Immune-mediated Diseases, Istituto Superiore di Sanità, Rome
I. Dell'Eva
Affiliation:
Azienda Provinciale per i Servizi Sanitari, Direzione Igiene e Sanità Pubblica, Trento, Italy
F. Helfer
Affiliation:
Azienda Provinciale per i Servizi Sanitari, Direzione Igiene e Sanità Pubblica, Trento, Italy
M. L. Ricci
Affiliation:
Department of Infectious, Parasitic, and Immune-mediated Diseases, Istituto Superiore di Sanità, Rome
*
Department of Infectious, Parasitic, and Immune-mediated Diseases, Istituto Superiore di Sanità, Viale Regina Elena, 299– 00161- Rome, Italy ([email protected])

Abstract

In 2004, an outbreak of legionnaires disease occurred in a hospital in northern Italy with a water system that had been disinfected multiple times since 1990 and equipped with a continuous disinfecting system. Molecular typing linked the outbreak to contamination of the hospital water system and demonstrated the persistence of a predominant strain of Legionella pneumophila for 15 years.

Type
Concise Communications
Copyright
Copyright © The Society for Healthcare Epidemiology of America 2007

Access options

Get access to the full version of this content by using one of the access options below. (Log in options will check for institutional or personal access. Content may require purchase if you do not have access.)

References

1. Fields, BS, Benson, RF, Besser, RE. Legionella and Legionnaires' disease: 25 years of investigation. Clin Microbiol Rev 2002;15:506526.Google Scholar
2. O'Neill, E, Humphreys, H. Surveillance of hospital water and primary prevention of nosocomial legionellosis: what is the evidence? J Hosp Infect 2005;59:273279.CrossRefGoogle ScholarPubMed
3. Bernander, S, Jacobson, K, Lundholm, M. A hospital-associated outbreak of Legionnaires' disease caused by Legionella pneumophila serogroups 4 and 10 with a common genetic fingerprinting pattern. APMIS 2004;112:210217.Google Scholar
4. Bernander, S, Jacobson, K, Helbig, JH, Luck, PC, Lundholm, M. A hospital-associated outbreak of Legionnaires' disease caused by Legionella pneumophila serogroup 1 is characterized by stable genetic fingerprinting but variable monoclonal antibody patterns. J Clin Microbiol 2003;41:25032508.CrossRefGoogle ScholarPubMed
5. Stout, JE, Yu, VL. Experiences of the first 16 hospitals using copper-silver ionization for Legionella control: implications for the evaluation of other disinfection modalities. Infect Control Hosp Epidemiol 2003;24:563568.CrossRefGoogle ScholarPubMed
6. Vonberg, RP, Eckmanns, T, Bruderek, J, Ruden, H, Gastmeier, P. Use of terminal tap water filter systems for prevention of nosocomial legionellosis. J Hosp Infect 2005;60:159162.Google Scholar
7. Helbig, IH, Arder, S, Castellani Pastoris, M, et al. Pan-European study on culture-proven Legionnaires' disease: distribution of Legionella pneumophila serogroups and monoclonal subgroups. Eur J Clin Microbiol Infect Dis 2002;21:710716.Google Scholar
8. Health Protection Agency. The European Working Group sequence-based typing database for Legionella pneumophila. Available at: http://www.hpa.org.uk/cfi/bioinformatics/ewgli/ewglisbt.htm. Accessed June 21, 2007.Google Scholar
9. Ausubel, FM, Brent, R, Kingston, RE, et al. Current Protocols in Molecular Biology. Greene Publishing Associates and Wiley Interscience: New York;1994.Google Scholar
10. Storey, MV, Winiecka-Krusnell, J, Ashbolt, NJ, Stenstrom, TA. The efficacy of heat and chlorine treatment against thermotolerant Acanthamoebae and Legionellae . Scand J Infect Dis 2004;36:656662.Google Scholar
11. Helms, CM, Massanari, RM, Wenzel, RP, Pfaller, MA, Moyer, NP, Hall, N. Legionnaires' disease associated with a hospital water system: a five-year progress report on continuous hyperchlorination. JAMA 1988;259:24232427.Google Scholar
12. Muraca, P, Stout, JE, Yu, VL. Comparative assessment of chlorine, heat, ozone, and UV light for killing Legionella pneumophila within a model plumbing system. Appl Environ Microbiol 1987;53:447453.Google Scholar
13. Srinivasan, A, Bova, G, Ross, T, et al. A 17-month evaluation of a chlorine dioxide water treatment system to control Legionella species in a hospital water supply. Infect Control Hosp Epidemiol 2003;24:575579.Google Scholar
14. Chien, M, Morozova, I, Shi, S, et al. The genomic sequence of the accidental pathogen Legionella pneumophila . Science 2004;305:19661968.Google Scholar